K-10.5M2 correlation leak detector
Determining the leak coordinates from the signals of two vibration sensors with data transmitted over radio channels.
We will agree on the configuration, delivery times and final cost before you order. In case of a fault, contact us about a return within 30 days of receipt. Terms are agreed individually.
Capabilities and applications
Locating a leak between two sensors
The K-10.5M2 is used on water pipes, heating networks and other pipelines. Two VDM-6 sensors are attached at the ends of the section under study, and the software calculates the damage coordinate from the correlation of the received signals.
Measurement and analysis
Radio units A and C transmit signals to the operator unit. The computer connects via USB. The software shows signals and spectra, records measurements and allows correlation functions to be re-analyzed.
The manufacturer's stated error of up to 0.5 m with a probability of 0.95 applies to heating networks up to 600 m long and up to 1200 mm in diameter when its comprehensive methodology is used.
Field work kit
The basic kit includes a Windows tablet-based operator unit, two radio units A and C, two VDM-6 vibration sensors, cables and chargers. An extended package is agreed separately.
Warranty on the device and software - 1 year; batteries are not covered by the warranty.
Specifications
| Parameter | Value |
|---|---|
| Radio channel range | 1000 m |
| Frequency range | 100-5000 Hz |
| Pipeline diameter | 50-1200 mm |
| Computer | PC-compatible; Windows 10 |
| RAM / SSD | From 2 GB / from 64 GB |
| Display | Color LCD, 11″ |
| Batteries of the unit and radio units | Built-in lithium-polymer, 7.4 V |
| Computer power supply | Standard battery; 220 V mains |
| Chargers | 220 V mains |
| Radio units in transmit mode | Up to 8 h |
| Unit on standby | Up to 8 h without a computer |
| Computer battery life | Typically 6-8 hours, depending on the mode |
| VDM-6 operating temperature | −30…+80 °C continuous; up to +120 °C for no more than 15 min |
| Radio unit temperature | −10…+50 °C |
| Operator unit temperature | −15…+50 °C; except the computer |
| System unit | 350 × 250 × 140 mm; no more than 5.5 kg |
| Radio unit | 277 × 98 × 78 mm; no more than 2 kg |
| Radio units with accessories laid out | 435 × 320 × 135 mm; no more than 7 kg |
Configuration
- Tablet-based operator unit with software
- Radio units A and C - 2 pcs.
- VDM-6 vibration sensors - 2 pcs.
- Cables, 6 m - 2 pcs.
- Radio unit chargers - 2 pcs.
- Operating manual
We confirm the final package contents before you order.